Skip to Content

Dry cooler BC/BD-t-2x480GC5-B03 C

Dry cooler BC/BD-t-2x480GC5-B03 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-t-2x480GC5-B03 C

Heat rejection i
243.28 kW
Air flow
59,016 m³/h
Fans
8 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 59,016 m³/h
External surface 726.2 m²
Inner volume 106.7 dm³
Fin materialAluminium
Net weight 1,039 kg
Fans
Quantity 8
Diameter 800 mm
Speed 435 rpm
Power 2,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 12
Acoustic
Sound pressure 41.0 dB(A)
Sound power 73.0 dB(A)
Energy class C
Connections
Inlet 3"
Outlet 3"
Defrost
BC/BD-t-2x480GC5-B03 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
243.281 kW Fluid flow 42.19 m³/h Pressure drop 78.4 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
180.026 kW Fluid flow 31.23 m³/h Pressure drop 45.9 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 147.38 not rated not rated not rated not rated not rated
40 243.28 147.72 not rated not rated not rated not rated
45 336.34 243.08 148.09 not rated not rated not rated
50 428.45 335.69 243.05 148.55 not rated not rated
55 520.13 427.39 335.34 243.28 149.15 not rated
60 611.57 518.67 426.74 335.37 243.82 149.95

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 110.39 not rated not rated not rated not rated not rated
40 180.03 110.66 not rated not rated not rated not rated
45 247.41 179.91 110.98 not rated not rated not rated
50 314.07 246.99 179.95 111.37 not rated not rated
55 380.39 313.37 246.82 180.19 111.90 not rated
60 446.53 379.43 313.02 246.97 180.72 112.60

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 243.281 42.19 78.4
Low speed (Y) 180.026 31.23 45.9

Dimensions

Dimension drawing of BC/BD-t-2x480GC5-B03 C
Dimension drawing
Dimensions as drawn
A 4550 mm
B 1450 mm
C 2310 mm
F 1150 mm
G 550 mm
E 4300 mm
H 1050 mm
I 2260 mm
K 4850 mm
D IN 3"
D OUT 3"
Overall [mm]
Length 4850 mm
Width 2310 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.