Skip to Content

Dry cooler BC/BD-463BB5-B19 C

Dry cooler BC/BD-463BB5-B19 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-463BB5-B19 C

Heat rejection i
107.64 kW
Air flow
47,350 m³/h
Fans
4 × ⌀630 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 47,350 m³/h
External surface 236.5 m²
Inner volume 39.8 dm³
Fin materialAluminium
Net weight 371 kg
Fans
Quantity 4
Diameter 630 mm
Speed 1,330 rpm
Power 5,000 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 58.0 dB(A)
Sound power 90.0 dB(A)
Energy class E
Connections
Inlet 3"
Outlet 3"
Defrost
BC/BD-463BB5-B19 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
107.635 kW Fluid flow 18.68 m³/h Pressure drop 32.6 kPa
Heat rejection · Low speed (Y)
92.554 kW Fluid flow 16.06 m³/h Pressure drop 25.0 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 60.25 not rated not rated not rated not rated not rated
40 107.64 60.73 not rated not rated not rated not rated
45 154.03 107.84 61.14 not rated not rated not rated
50 200.13 154.02 108.02 61.51 not rated not rated
55 246.08 199.90 154.01 108.21 61.85 not rated
60 291.97 245.66 199.72 154.04 108.41 62.18

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 52.00 not rated not rated not rated not rated not rated
40 92.55 52.43 not rated not rated not rated not rated
45 132.16 92.72 52.79 not rated not rated not rated
50 171.48 132.13 92.88 53.11 not rated not rated
55 210.67 171.27 132.12 93.04 53.42 not rated
60 249.79 210.29 171.11 132.15 93.23 53.72

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 107.635 18.68 32.6
Low speed (Y) 92.554 16.06 25.0

Dimensions

Dimension drawing of BC/BD-463BB5-B19 C
Dimension drawing
Dimensions as drawn
A 3950 mm
B 1220 mm
C 1230 mm
F 1050 mm
G 450 mm
E 3700 mm
H 900 mm
I 1180 mm
K 4200 mm
D IN 3"
D OUT 3"
Overall [mm]
Length 3950 mm
Width 1230 mm
Height 1220 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.