BC/BD-380CD1-B03 C
120.51 kW
Defrost: None
Product code: BC/BD-463BD1-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 31,456 m³/h |
|---|---|
| External surface | 465.3 m² |
| Inner volume | 57.4 dm³ |
| Fin material | Aluminium |
| Net weight | 430 kg |
| Quantity | 4 |
|---|---|
| Diameter | 630 mm |
| Speed | 860 rpm |
| Power | 2,400 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 49.0 dB(A) |
|---|---|
| Sound power | 80.5 dB(A) |
| Energy class | D |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BC/BD-463BD1-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 71.64 | not rated | not rated | not rated | not rated | not rated |
| 40 | 120.24 | 71.81 | not rated | not rated | not rated | not rated |
| 45 | 167.44 | 120.05 | 71.97 | not rated | not rated | not rated |
| 50 | 214.18 | 166.95 | 119.92 | 72.14 | not rated | not rated |
| 55 | 260.70 | 213.41 | 166.58 | 119.88 | 72.36 | not rated |
| 60 | 307.10 | 259.66 | 212.81 | 166.37 | 119.97 | 72.63 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 120.239 | 20.85 | 49.5 |
| A | 3950 mm |
|---|---|
| B | 1220 mm |
| C | 1230 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 3700 mm |
| H | 900 mm |
| I | 1180 mm |
| K | 4200 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 3950 mm |
|---|---|
| Width | 1230 mm |
| Height | 1220 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.