BC/BD-2X263BD1-B01 C
119.51 kW
Defrost: None
Product code: BC/BD-463CD5-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 31,877 m³/h |
|---|---|
| External surface | 522.3 m² |
| Inner volume | 73.8 dm³ |
| Fin material | Aluminium |
| Net weight | 481 kg |
| Quantity | 4 |
|---|---|
| Diameter | 630 mm |
| Speed | 860 rpm |
| Power | 2,400 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 49.0 dB(A) |
|---|---|
| Sound power | 80.4 dB(A) |
| Energy class | D |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| BC/BD-463CD5-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 71.14 | not rated | not rated | not rated | not rated | not rated |
| 40 | 119.81 | 71.31 | not rated | not rated | not rated | not rated |
| 45 | 167.13 | 119.63 | 71.46 | not rated | not rated | not rated |
| 50 | 213.99 | 166.64 | 119.50 | 71.63 | not rated | not rated |
| 55 | 260.64 | 213.23 | 166.27 | 119.46 | 71.84 | not rated |
| 60 | 307.18 | 259.60 | 212.62 | 166.05 | 119.54 | 72.13 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 119.809 | 20.78 | 41.2 |
| A | 3900 mm |
|---|---|
| B | 1200 mm |
| C | 1240 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 3700 mm |
| H | 900 mm |
| I | 1190 mm |
| K | 4200 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 4200 mm |
|---|---|
| Width | 1240 mm |
| Height | 1200 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.