BC/BD-2X463CA5-B01 C
155.20 kW
Defrost: None
Product code: BC/BD-480FC1-B03 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 36,162 m³/h |
|---|---|
| External surface | 912.2 m² |
| Inner volume | 165.7 dm³ |
| Fin material | Aluminium |
| Net weight | 868 kg |
| Quantity | 4 |
|---|---|
| Diameter | 800 mm |
| Speed | 435 rpm |
| Power | 1,300 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 12 |
| Sound pressure | 38.0 dB(A) |
|---|---|
| Sound power | 70.0 dB(A) |
| Energy class | B |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| BC/BD-480FC1-B03 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 95.38 | not rated | not rated | not rated | not rated | not rated |
| 40 | 155.15 | 95.23 | not rated | not rated | not rated | not rated |
| 45 | 213.24 | 154.54 | 95.13 | not rated | not rated | not rated |
| 50 | 270.77 | 212.20 | 154.06 | 95.10 | not rated | not rated |
| 55 | 328.04 | 269.32 | 211.37 | 153.74 | 95.18 | not rated |
| 60 | 385.18 | 326.20 | 268.16 | 210.79 | 153.64 | 95.40 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 72.91 | not rated | not rated | not rated | not rated | not rated |
| 40 | 117.43 | 72.75 | not rated | not rated | not rated | not rated |
| 45 | 160.62 | 116.88 | 72.62 | not rated | not rated | not rated |
| 50 | 203.40 | 159.73 | 116.43 | 72.55 | not rated | not rated |
| 55 | 245.97 | 202.17 | 158.99 | 116.12 | 72.58 | not rated |
| 60 | 288.45 | 244.43 | 201.16 | 158.47 | 115.99 | 72.72 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 155.152 | 26.90 | 63.0 |
| Low speed (Y) | 117.428 | 20.37 | 38.4 |
| A | 7350 mm |
|---|---|
| B | 1450 mm |
| C | 1240 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 7100 mm |
| H | 1750 mm |
| I | 1190 mm |
| K | 7650 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 7650 mm |
|---|---|
| Width | 1240 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.