BC/BD-t-563AC5-B01 C
154.66 kW
Defrost: None
Product code: BC/BD-t-2X363AA5-B19 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 72,170 m³/h |
|---|---|
| External surface | 233.4 m² |
| Inner volume | 50.9 dm³ |
| Fin material | Aluminium |
| Net weight | 446 kg |
| Quantity | 6 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 7,500 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 60.0 dB(A) |
|---|---|
| Sound power | 92.0 dB(A) |
| Energy class | E |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BC/BD-t-2X363AA5-B19 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 87.09 | not rated | not rated | not rated | not rated | not rated |
| 40 | 154.83 | 87.65 | not rated | not rated | not rated | not rated |
| 45 | 221.38 | 155.05 | 88.12 | not rated | not rated | not rated |
| 50 | 287.57 | 221.31 | 155.25 | 88.55 | not rated | not rated |
| 55 | 353.57 | 287.22 | 221.26 | 155.46 | 88.96 | not rated |
| 60 | 419.49 | 352.96 | 286.93 | 221.27 | 155.71 | 89.36 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 76.22 | not rated | not rated | not rated | not rated | not rated |
| 40 | 134.90 | 76.71 | not rated | not rated | not rated | not rated |
| 45 | 192.47 | 135.10 | 77.13 | not rated | not rated | not rated |
| 50 | 249.68 | 192.40 | 135.27 | 77.51 | not rated | not rated |
| 55 | 306.73 | 249.36 | 192.35 | 135.45 | 77.87 | not rated |
| 60 | 363.69 | 306.17 | 249.10 | 192.36 | 135.68 | 78.24 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 154.830 | 26.87 | 72.7 |
| Low speed (Y) | 134.903 | 23.41 | 57.0 |
| A | 3050 mm |
|---|---|
| B | 1220 mm |
| C | 2310 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 2800 mm |
| H | 900 mm |
| I | 2260 mm |
| K | 3300 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 3050 mm |
|---|---|
| Width | 2310 mm |
| Height | 1220 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.