BC/BD-t-563AC5-B01 C
154.66 kW
Defrost: None
Product code: BC/BD-480OB5-B03 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 41,692 m³/h |
|---|---|
| External surface | 794.9 m² |
| Inner volume | 173.6 dm³ |
| Fin material | Aluminium |
| Net weight | 942 kg |
| Quantity | 4 |
|---|---|
| Diameter | 800 mm |
| Speed | 435 rpm |
| Power | 1,300 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 12 |
| Sound pressure | 37.0 dB(A) |
|---|---|
| Sound power | 70.0 dB(A) |
| Energy class | B |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BC/BD-480OB5-B03 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 91.92 | not rated | not rated | not rated | not rated | not rated |
| 40 | 154.65 | 91.98 | not rated | not rated | not rated | not rated |
| 45 | 215.66 | 154.17 | 92.02 | not rated | not rated | not rated |
| 50 | 276.11 | 214.71 | 153.76 | 92.09 | not rated | not rated |
| 55 | 336.30 | 274.70 | 213.89 | 153.45 | 92.20 | not rated |
| 60 | 396.33 | 334.44 | 273.50 | 213.26 | 153.30 | 92.40 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 73.74 | not rated | not rated | not rated | not rated | not rated |
| 40 | 123.14 | 73.79 | not rated | not rated | not rated | not rated |
| 45 | 171.06 | 122.73 | 73.82 | not rated | not rated | not rated |
| 50 | 218.50 | 170.27 | 122.39 | 73.88 | not rated | not rated |
| 55 | 265.71 | 217.34 | 169.60 | 122.14 | 73.97 | not rated |
| 60 | 312.79 | 264.20 | 216.36 | 169.08 | 122.01 | 74.14 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 154.646 | 26.82 | 22.2 |
| Low speed (Y) | 123.139 | 21.36 | 14.8 |
| A | 9950 mm |
|---|---|
| B | 1450 mm |
| C | 1240 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 9700 mm |
| H | 2400 mm |
| I | 1190 mm |
| K | 10250 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 10250 mm |
|---|---|
| Width | 1240 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.