Skip to Content

Dry cooler BC/BD-463BD1-B19 C

Dry cooler BC/BD-463BD1-B19 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-463BD1-B19 C

Heat rejection i
154.40 kW
Air flow
43,433 m³/h
Fans
4 × ⌀630 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 43,433 m³/h
External surface 465.3 m²
Inner volume 57.4 dm³
Fin materialAluminium
Net weight 428 kg
Fans
Quantity 4
Diameter 630 mm
Speed 1,330 rpm
Power 5,000 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 57.0 dB(A)
Sound power 89.0 dB(A)
Energy class E
Connections
Inlet 3"
Outlet 3"
Defrost
BC/BD-463BD1-B19 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
154.396 kW Fluid flow 26.80 m³/h Pressure drop 77.1 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
127.167 kW Fluid flow 22.05 m³/h Pressure drop 54.6 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 91.15 not rated not rated not rated not rated not rated
40 154.40 91.35 not rated not rated not rated not rated
45 215.97 154.16 91.53 not rated not rated not rated
50 277.01 215.33 153.97 91.73 not rated not rated
55 337.80 276.01 214.83 153.86 91.96 not rated
60 398.45 336.43 275.19 214.49 153.91 92.27

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 75.62 not rated not rated not rated not rated not rated
40 127.17 75.85 not rated not rated not rated not rated
45 177.27 127.07 76.04 not rated not rated not rated
50 226.89 176.89 126.98 76.20 not rated not rated
55 276.28 226.26 176.58 126.91 76.41 not rated
60 325.56 275.41 225.72 176.29 126.96 76.69

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 154.396 26.80 77.1
Low speed (Y) 127.167 22.05 54.6

Dimensions

Dimension drawing of BC/BD-463BD1-B19 C
Dimension drawing
Dimensions as drawn
A 3950 mm
B 1220 mm
C 1230 mm
F 1050 mm
G 450 mm
E 3700 mm
H 900 mm
I 1180 mm
K 4200 mm
D IN 3"
D OUT 3"
Overall [mm]
Length 3950 mm
Width 1230 mm
Height 1220 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.