Skip to Content

Dry cooler BC/BD-580DD5-B03 C

Dry cooler BC/BD-580DD5-B03 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-580DD5-B03 C

Heat rejection i
154.33 kW
Air flow
36,404 m³/h
Fans
5 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 36,404 m³/h
External surface 828.0 m²
Inner volume 176.8 dm³
Fin materialAluminium
Net weight 903 kg
Fans
Quantity 5
Diameter 800 mm
Speed 435 rpm
Power 1,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 12
Acoustic
Sound pressure 39.0 dB(A)
Sound power 71.0 dB(A)
Energy class C
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
BC/BD-580DD5-B03 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
154.326 kW Fluid flow 26.76 m³/h Pressure drop 39.3 kPa
Heat rejection · Low speed (Y)
112.817 kW Fluid flow 19.57 m³/h Pressure drop 22.4 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 94.30 not rated not rated not rated not rated not rated
40 154.33 94.45 not rated not rated not rated not rated
45 212.59 154.14 94.64 not rated not rated not rated
50 270.26 212.12 154.08 94.88 not rated not rated
55 327.67 269.53 211.85 154.19 95.24 not rated
60 384.93 326.69 269.08 211.85 154.51 95.73

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 69.74 not rated not rated not rated not rated not rated
40 112.82 69.95 not rated not rated not rated not rated
45 154.55 112.85 70.11 not rated not rated not rated
50 195.85 154.46 112.85 70.34 not rated not rated
55 236.94 195.64 154.33 112.99 70.65 not rated
60 277.93 236.63 195.40 154.41 113.31 71.08

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 154.326 26.76 39.3
Low speed (Y) 112.817 19.57 22.4

Dimensions

Dimension drawing of BC/BD-580DD5-B03 C
Dimension drawing
Dimensions as drawn
A 6350 mm
B 1450 mm
C 1240 mm
F 1150 mm
G 550 mm
E 6100 mm
H 1200 mm
I 1190 mm
K 6650 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 6650 mm
Width 1240 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.