BC/BD-t-463AA1-B19 C
115.12 kW
Defrost: None
Product code: BC/BD-480HD1-B03 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 28,499 m³/h |
|---|---|
| External surface | 542.8 m² |
| Inner volume | 57.2 dm³ |
| Fin material | Aluminium |
| Net weight | 627 kg |
| Quantity | 4 |
|---|---|
| Diameter | 800 mm |
| Speed | 435 rpm |
| Power | 1,300 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 12 |
| Sound pressure | 38.0 dB(A) |
|---|---|
| Sound power | 70.0 dB(A) |
| Energy class | C |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| BC/BD-480HD1-B03 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 69.52 | not rated | not rated | not rated | not rated | not rated |
| 40 | 115.08 | 69.71 | not rated | not rated | not rated | not rated |
| 45 | 159.32 | 115.06 | 69.94 | not rated | not rated | not rated |
| 50 | 203.11 | 159.10 | 115.11 | 70.20 | not rated | not rated |
| 55 | 246.70 | 202.72 | 159.02 | 115.27 | 70.52 | not rated |
| 60 | 290.18 | 246.14 | 202.51 | 159.11 | 115.58 | 70.94 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | not rated | not rated | not rated | not rated | not rated | not rated |
| 40 | not rated | not rated | not rated | not rated | not rated | not rated |
| 45 | not rated | not rated | 52.00 | not rated | not rated | not rated |
| 50 | not rated | not rated | 84.69 | 52.17 | not rated | not rated |
| 55 | not rated | not rated | 116.39 | 84.76 | 52.51 | not rated |
| 60 | not rated | not rated | 147.78 | 116.39 | 85.15 | 52.87 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 115.082 | 19.96 | 63.3 |
| Low speed (Y) | — | — | — |
| A | 4550 mm |
|---|---|
| B | 1450 mm |
| C | 1230 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 4300 mm |
| H | 1050 mm |
| I | 1180 mm |
| K | 4850 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 4850 mm |
|---|---|
| Width | 1230 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.