Skip to Content

Dry cooler BC/BD-t-463AA1-B19 C

Dry cooler BC/BD-t-463AA1-B19 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-t-463AA1-B19 C

Heat rejection i
115.12 kW
Air flow
47,739 m³/h
Fans
4 × ⌀630 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 47,739 m³/h
External surface 186.1 m²
Inner volume 27.6 dm³
Fin materialAluminium
Net weight 351 kg
Fans
Quantity 4
Diameter 630 mm
Speed 1,330 rpm
Power 5,000 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 58.0 dB(A)
Sound power 90.0 dB(A)
Energy class E
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
BC/BD-t-463AA1-B19 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
115.120 kW Fluid flow 19.98 m³/h Pressure drop 62.0 kPa
Heat rejection · Low speed (Y)
99.583 kW Fluid flow 17.28 m³/h Pressure drop 47.9 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 64.48 not rated not rated not rated not rated not rated
40 115.12 64.94 not rated not rated not rated not rated
45 164.80 115.30 65.34 not rated not rated not rated
50 214.15 164.71 115.45 65.70 not rated not rated
55 263.38 213.82 164.64 115.61 66.03 not rated
60 312.52 262.81 213.55 164.63 115.80 66.37

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 56.07 not rated not rated not rated not rated not rated
40 99.58 56.47 not rated not rated not rated not rated
45 142.17 99.71 56.81 not rated not rated not rated
50 184.46 142.07 99.83 57.12 not rated not rated
55 226.61 184.14 142.00 99.97 57.42 not rated
60 268.68 226.08 183.89 141.99 100.16 57.73

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 115.120 19.98 62.0
Low speed (Y) 99.583 17.28 47.9

Dimensions

Dimension drawing of BC/BD-t-463AA1-B19 C
Dimension drawing
Dimensions as drawn
A 3950 mm
B 1220 mm
C 1230 mm
F 1050 mm
G 450 mm
E 3700 mm
H 900 mm
I 1180 mm
K 4200 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 3950 mm
Width 1230 mm
Height 1220 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.