Skip to Content

Dry cooler BC/BD-480OD5-B01 C

Dry cooler BC/BD-480OD5-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-480OD5-B01 C

Heat rejection i
313.67 kW
Air flow
78,675 m³/h
Fans
4 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 78,675 m³/h
External surface 1,324.8 m²
Inner volume 289.9 dm³
Fin materialAluminium
Net weight 1,143 kg
Fans
Quantity 4
Diameter 800 mm
Speed 900 rpm
Power 7,200 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 53.0 dB(A)
Sound power 86.0 dB(A)
Energy class D
Connections
Inlet 4"
Outlet 4"
Defrost
BC/BD-480OD5-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
313.672 kW Fluid flow 54.40 m³/h Pressure drop 31.1 kPa
Heat rejection · Low speed (Y)
238.276 kW Fluid flow 41.32 m³/h Pressure drop 19.0 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 188.19 not rated not rated not rated not rated not rated
40 313.67 188.27 not rated not rated not rated not rated
45 435.48 312.64 188.28 not rated not rated not rated
50 556.05 433.48 311.78 188.41 not rated not rated
55 676.04 553.12 431.80 311.18 188.68 not rated
60 795.72 672.22 550.67 430.57 310.94 189.16

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 144.50 not rated not rated not rated not rated not rated
40 238.28 144.48 not rated not rated not rated not rated
45 329.06 237.37 144.47 not rated not rated not rated
50 418.85 327.37 236.62 144.54 not rated not rated
55 508.17 416.43 325.99 236.11 144.73 not rated
60 597.24 505.04 414.44 324.98 235.90 145.10

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 313.672 54.40 31.1
Low speed (Y) 238.276 41.32 19.0

Dimensions

Dimension drawing of BC/BD-480OD5-B01 C
Dimension drawing
Dimensions as drawn
A 9950 mm
B 1450 mm
C 1240 mm
F 1150 mm
G 550 mm
E 9700 mm
H 2400 mm
I 1190 mm
K 10250 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 10250 mm
Width 1240 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.