BC/BD-2X563BB5-B19 C
272.10 kW
Defrost: None
Product code: BC/BD-491EC1-B04 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 89,812 m³/h |
|---|---|
| External surface | 768.8 m² |
| Inner volume | 102.5 dm³ |
| Fin material | Aluminium |
| Net weight | 781 kg |
| Quantity | 4 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 11,200 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 66.0 dB(A) |
|---|---|
| Sound power | 97.8 dB(A) |
| Energy class | E |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BC/BD-491EC1-B04 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 155.73 | not rated | not rated | not rated | not rated | not rated |
| 40 | 272.00 | 156.68 | not rated | not rated | not rated | not rated |
| 45 | 385.58 | 272.34 | 157.54 | not rated | not rated | not rated |
| 50 | 498.30 | 385.40 | 272.72 | 158.37 | not rated | not rated |
| 55 | 610.59 | 497.61 | 385.37 | 273.20 | 159.21 | not rated |
| 60 | 722.66 | 609.44 | 497.17 | 385.54 | 273.85 | 160.12 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 271.996 | 47.21 | 55.2 |
| A | 5950 mm |
|---|---|
| B | 1450 mm |
| C | 1240 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 5700 mm |
| H | 1400 mm |
| I | 1190 mm |
| K | 6250 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 6250 mm |
|---|---|
| Width | 1240 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.