Skip to Content

Dry cooler BC/BD-580AC5-B01 C

Dry cooler BC/BD-580AC5-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-580AC5-B01 C

Heat rejection i
244.72 kW
Air flow
84,352 m³/h
Fans
5 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 84,352 m³/h
External surface 696.4 m²
Inner volume 108.1 dm³
Fin materialAluminium
Net weight 843 kg
Fans
Quantity 5
Diameter 800 mm
Speed 900 rpm
Power 9,000 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 56.0 dB(A)
Sound power 88.0 dB(A)
Energy class E
Connections
Inlet 4"
Outlet 4"
Defrost
BC/BD-580AC5-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
244.719 kW Fluid flow 42.47 m³/h Pressure drop 48.7 kPa
Heat rejection · Low speed (Y)
195.432 kW Fluid flow 33.92 m³/h Pressure drop 32.7 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 140.41 not rated not rated not rated not rated not rated
40 244.72 141.24 not rated not rated not rated not rated
45 346.74 245.09 141.99 not rated not rated not rated
50 448.02 346.70 245.46 142.71 not rated not rated
55 548.94 447.60 346.74 245.91 143.45 not rated
60 649.67 548.16 447.33 346.97 246.51 144.26

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 113.14 not rated not rated not rated not rated not rated
40 195.43 113.75 not rated not rated not rated not rated
45 275.65 195.58 114.30 not rated not rated not rated
50 355.19 275.40 195.76 114.83 not rated not rated
55 434.42 354.59 275.29 196.05 115.41 not rated
60 513.48 433.47 354.18 275.35 196.47 116.04

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 244.719 42.47 48.7
Low speed (Y) 195.432 33.92 32.7

Dimensions

Dimension drawing of BC/BD-580AC5-B01 C
Dimension drawing
Dimensions as drawn
A 6350 mm
B 1450 mm
C 1240 mm
F 1150 mm
G 550 mm
E 6100 mm
H 1200 mm
I 1190 mm
K 6650 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 6350 mm
Width 1240 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.