BC/BD-2X463CA5-B01 C
155.20 kW
Defrost: None
Product code: BC/BD-580DD1-B03 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 34,942 m³/h |
|---|---|
| External surface | 977.3 m² |
| Inner volume | 176.8 dm³ |
| Fin material | Aluminium |
| Net weight | 928 kg |
| Quantity | 5 |
|---|---|
| Diameter | 800 mm |
| Speed | 435 rpm |
| Power | 1,600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 12 |
| Sound pressure | 39.0 dB(A) |
|---|---|
| Sound power | 71.0 dB(A) |
| Energy class | C |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| BC/BD-580DD1-B03 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 96.21 | not rated | not rated | not rated | not rated | not rated |
| 40 | 155.71 | 96.30 | not rated | not rated | not rated | not rated |
| 45 | 213.35 | 155.44 | 96.44 | not rated | not rated | not rated |
| 50 | 270.39 | 212.78 | 155.31 | 96.67 | not rated | not rated |
| 55 | 327.16 | 269.54 | 212.44 | 155.38 | 97.02 | not rated |
| 60 | 383.77 | 326.04 | 269.00 | 212.39 | 155.70 | 97.53 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | not rated | not rated | not rated | not rated | not rated | not rated |
| 40 | not rated | not rated | not rated | not rated | not rated | not rated |
| 45 | not rated | not rated | not rated | not rated | not rated | not rated |
| 50 | not rated | not rated | not rated | not rated | not rated | not rated |
| 55 | not rated | not rated | not rated | not rated | not rated | not rated |
| 60 | not rated | not rated | not rated | not rated | not rated | 71.18 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 155.711 | 27.01 | 40.0 |
| Low speed (Y) | — | — | — |
| A | 6350 mm |
|---|---|
| B | 1450 mm |
| C | 1240 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 6100 mm |
| H | 1200 mm |
| I | 1190 mm |
| K | 6650 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 6650 mm |
|---|---|
| Width | 1240 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.