Skip to Content

Dry cooler BC/BD-580FB5-B03 C

Dry cooler BC/BD-580FB5-B03 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-580FB5-B03 C

Heat rejection i
173.17 kW
Air flow
48,725 m³/h
Fans
5 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 48,725 m³/h
External surface 724.5 m²
Inner volume 155.9 dm³
Fin materialAluminium
Net weight 959 kg
Fans
Quantity 5
Diameter 800 mm
Speed 435 rpm
Power 1,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 12
Acoustic
Sound pressure 38.0 dB(A)
Sound power 71.0 dB(A)
Energy class C
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
BC/BD-580FB5-B03 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
173.172 kW Fluid flow 30.05 m³/h Pressure drop 71.9 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
135.185 kW Fluid flow 23.45 m³/h Pressure drop 46.2 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 103.47 not rated not rated not rated not rated not rated
40 173.17 103.48 not rated not rated not rated not rated
45 241.21 172.74 103.50 not rated not rated not rated
50 308.72 240.36 172.38 103.55 not rated not rated
55 375.98 307.46 239.65 172.13 103.68 not rated
60 443.10 374.34 306.43 239.16 172.06 103.88

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 81.46 not rated not rated not rated not rated not rated
40 135.19 81.44 not rated not rated not rated not rated
45 187.55 134.80 81.45 not rated not rated not rated
50 239.46 186.82 134.49 81.48 not rated not rated
55 291.16 238.42 186.24 134.30 81.61 not rated
60 342.75 289.80 237.56 185.83 134.28 81.83

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 173.172 30.05 71.9
Low speed (Y) 135.185 23.45 46.2

Dimensions

Dimension drawing of BC/BD-580FB5-B03 C
Dimension drawing
Dimensions as drawn
A 9100 mm
B 1450 mm
C 1240 mm
F 1150 mm
G 550 mm
E 8850 mm
H 1750 mm
I 1190 mm
K 9400 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 9400 mm
Width 1240 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.