Skip to Content

Dry cooler BC/BD-t-2X363AA1-B19 C

Dry cooler BC/BD-t-2X363AA1-B19 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-t-2X363AA1-B19 C

Heat rejection i
173.40 kW
Air flow
71,450 m³/h
Fans
6 × ⌀630 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Model nomenclature

How to read the code of this model.

  • A
    Series: BC/BD — BC = vertical, BD = horizontal dry cooler (air flow bottom to top).
  • B
    Fin type (optional "t"): t — t: louvered fins (high-efficiency fin surface)
  • C
    Fan rows (optional "Nx"): 2 — Catalogue: "Fan Row no." (number before x/X).
  • D
    Number of fans per row: 3 — Digit 1-9; total fans = fan rows x this digit.
  • E
    Fan diameter: 63 — Ø630 mm
  • G
    Coil tube rows (2nd dimensional letter): A — 2 tube rows
  • H
    Fin spacing: 1 — 2.1 mm
  • I
    Generation code: B — generation B
  • J
    Fan data (fan motor code): 19 — three-phase 400 V 50 Hz, 4-pole AC fan (in this series)

Data

Coil
Air flow 71,450 m³/h
External surface 275.6 m²
Inner volume 50.9 dm³
Fin materialAluminium
Net weight 452 kg
Fans
Quantity 6
Diameter 630 mm
Speed 1,330 rpm
Power 7,500 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 60.0 dB(A)
Sound power 92.0 dB(A)
Energy class E
Connections
Inlet 3"
Outlet 3"
Defrost
BC/BD-t-2X363AA1-B19 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
173.399 kW Fluid flow 30.10 m³/h Pressure drop 88.9 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
149.930 kW Fluid flow 26.02 m³/h Pressure drop 68.7 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 97.96 not rated not rated not rated not rated not rated
40 173.40 98.54 not rated not rated not rated not rated
45 247.42 173.57 99.03 not rated not rated not rated
50 320.98 247.22 173.72 99.48 not rated not rated
55 394.35 320.43 247.05 173.89 99.91 not rated
60 467.59 393.46 319.98 246.98 174.12 100.35

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 85.15 not rated not rated not rated not rated not rated
40 149.93 85.64 not rated not rated not rated not rated
45 213.38 150.05 86.06 not rated not rated not rated
50 276.40 213.17 150.16 86.46 not rated not rated
55 339.22 275.88 213.00 150.31 86.84 not rated
60 401.93 338.39 275.45 212.94 150.53 87.25

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 173.399 30.10 88.9
Low speed (Y) 149.930 26.02 68.7

Dimensions

Dimension drawing of BC/BD-t-2X363AA1-B19 C
Dimension drawing
Dimensions as drawn
A 3050 mm
B 1220 mm
C 2310 mm
F 1050 mm
G 450 mm
E 2800 mm
H 900 mm
I 2260 mm
K 3300 mm
D IN 3"
D OUT 3"
Overall [mm]
Length 3050 mm
Width 2310 mm
Height 1220 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.