BC/BD-563BB1-B19 C
151.56 kW
Defrost: None
Product code: BC/BD-580HA1-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 92,735 m³/h |
|---|---|
| External surface | 271.4 m² |
| Inner volume | 39.1 dm³ |
| Fin material | Aluminium |
| Net weight | 680 kg |
| Quantity | 5 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 9,000 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 55.0 dB(A) |
|---|---|
| Sound power | 87.5 dB(A) |
| Energy class | E |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BC/BD-580HA1-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 81.22 | not rated | not rated | not rated | not rated | not rated |
| 40 | 151.49 | 82.47 | not rated | not rated | not rated | not rated |
| 45 | 220.46 | 152.44 | 83.54 | not rated | not rated | not rated |
| 50 | 289.11 | 221.22 | 153.28 | 84.49 | not rated | not rated |
| 55 | 357.60 | 289.71 | 221.94 | 154.09 | 85.37 | not rated |
| 60 | 426.00 | 358.05 | 290.31 | 222.66 | 154.89 | 86.20 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 67.12 | not rated | not rated | not rated | not rated | not rated |
| 40 | 124.65 | 68.15 | not rated | not rated | not rated | not rated |
| 45 | 180.94 | 125.38 | 69.04 | not rated | not rated | not rated |
| 50 | 236.88 | 181.48 | 126.04 | 69.82 | not rated | not rated |
| 55 | 292.67 | 237.25 | 181.99 | 126.67 | 70.54 | not rated |
| 60 | 348.38 | 292.91 | 237.65 | 182.52 | 127.29 | 71.22 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 151.492 | 26.29 | 27.4 |
| Low speed (Y) | 124.651 | 21.63 | 19.4 |
| A | 5600 mm |
|---|---|
| B | 1450 mm |
| C | 1230 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 5350 mm |
| H | 1050 mm |
| I | 1180 mm |
| K | 5900 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 5600 mm |
|---|---|
| Width | 1230 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.