BC/BD-t-363AC5-B19 C
118.30 kW
Defrost: None
Product code: BC/BD-580HB5-B03 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 43,196 m³/h |
|---|---|
| External surface | 344.8 m² |
| Inner volume | 48.5 dm³ |
| Fin material | Aluminium |
| Net weight | 690 kg |
| Quantity | 5 |
|---|---|
| Diameter | 800 mm |
| Speed | 435 rpm |
| Power | 1,600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 12 |
| Sound pressure | 39.0 dB(A) |
|---|---|
| Sound power | 71.0 dB(A) |
| Energy class | C |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| BC/BD-580HB5-B03 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 68.39 | not rated | not rated | not rated | not rated | not rated |
| 40 | 118.30 | 68.75 | not rated | not rated | not rated | not rated |
| 45 | 167.14 | 118.46 | 69.08 | not rated | not rated | not rated |
| 50 | 215.63 | 167.14 | 118.64 | 69.40 | not rated | not rated |
| 55 | 263.96 | 215.48 | 167.19 | 118.86 | 69.73 | not rated |
| 60 | 312.22 | 263.68 | 215.42 | 167.34 | 119.15 | 70.10 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 54.84 | not rated | not rated | not rated | not rated | not rated |
| 40 | 94.29 | 55.12 | not rated | not rated | not rated | not rated |
| 45 | 132.79 | 94.38 | 55.38 | not rated | not rated | not rated |
| 50 | 170.99 | 132.74 | 94.50 | 55.63 | not rated | not rated |
| 55 | 209.05 | 170.80 | 132.74 | 94.66 | 55.89 | not rated |
| 60 | 247.04 | 208.73 | 170.70 | 132.83 | 94.88 | 56.19 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 118.301 | 20.53 | 56.5 |
| Low speed (Y) | 94.291 | 16.36 | 37.8 |
| A | 5600 mm |
|---|---|
| B | 1450 mm |
| C | 1230 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 5350 mm |
| H | 1050 mm |
| I | 1180 mm |
| K | 5900 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 5900 mm |
|---|---|
| Width | 1230 mm |
| Height | 1450 mm |