Skip to Content

Dry cooler BC/BD-t-363AC5-B19 C

Dry cooler BC/BD-t-363AC5-B19 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-t-363AC5-B19 C

Heat rejection i
118.30 kW
Air flow
33,225 m³/h
Fans
3 × ⌀630 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 33,225 m³/h
External surface 236.5 m²
Inner volume 36.4 dm³
Fin materialAluminium
Net weight 307 kg
Fans
Quantity 3
Diameter 630 mm
Speed 1,330 rpm
Power 3,800 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 56.0 dB(A)
Sound power 88.0 dB(A)
Energy class E
Connections
Inlet 2 1/2"
Outlet 2 1/2"
Defrost
BC/BD-t-363AC5-B19 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
118.299 kW Fluid flow 20.53 m³/h Pressure drop 98.9 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
98.357 kW Fluid flow 17.06 m³/h Pressure drop 71.2 kPa above the recommended pressure drop

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 69.81 not rated not rated not rated not rated not rated
40 118.30 69.92 not rated not rated not rated not rated
45 165.53 118.07 70.03 not rated not rated not rated
50 212.35 164.97 117.87 70.15 not rated not rated
55 258.99 211.50 164.52 117.75 70.30 not rated
60 305.51 257.83 210.78 164.19 117.73 70.51

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 58.51 not rated not rated not rated not rated not rated
40 98.36 58.60 not rated not rated not rated not rated
45 137.11 98.15 58.68 not rated not rated not rated
50 175.49 136.63 97.98 58.78 not rated not rated
55 213.69 174.75 136.24 97.88 58.92 not rated
60 251.80 212.71 174.15 135.97 97.89 59.09

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 118.299 20.53 98.9
Low speed (Y) 98.357 17.06 71.2

Dimensions

Dimension drawing of BC/BD-t-363AC5-B19 C
Dimension drawing
Dimensions as drawn
A 3050 mm
B 1220 mm
C 1230 mm
F 1050 mm
G 450 mm
E 2800 mm
H 900 mm
I 1180 mm
K 3300 mm
D IN 2 1/2"
D OUT 2 1/2"
Overall [mm]
Length 3050 mm
Width 1230 mm
Height 1220 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.