BC/BD-2x380NB1-B01 C
405.84 kW
Defrost: None
Product code: BC/BD-591DD5-B04 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 113,217 m³/h |
|---|---|
| External surface | 1,207.5 m² |
| Inner volume | 266.2 dm³ |
| Fin material | Aluminium |
| Net weight | 1,174 kg |
| Quantity | 5 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 14,000 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 66.0 dB(A) |
|---|---|
| Sound power | 98.7 dB(A) |
| Energy class | E |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BC/BD-591DD5-B04 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 238.91 | not rated | not rated | not rated | not rated | not rated |
| 40 | 405.80 | 239.65 | not rated | not rated | not rated | not rated |
| 45 | 568.25 | 405.50 | 240.37 | not rated | not rated | not rated |
| 50 | 729.28 | 567.01 | 405.36 | 241.10 | not rated | not rated |
| 55 | 889.62 | 727.17 | 566.13 | 405.41 | 241.95 | not rated |
| 60 | 1049.57 | 886.66 | 725.57 | 565.70 | 405.92 | 243.03 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 405.803 | 70.43 | 45.9 |
| A | 9100 mm |
|---|---|
| B | 1450 mm |
| C | 1240 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 8850 mm |
| H | 1750 mm |
| I | 1190 mm |
| K | 9400 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 9400 mm |
|---|---|
| Width | 1240 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.