Skip to Content

Dry cooler BC/BD-t-2X680GA5-B01 C

Dry cooler BC/BD-t-2X680GA5-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-t-2X680GA5-B01 C

Heat rejection i
406.22 kW
Air flow
216,056 m³/h
Fans
12 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 216,056 m³/h
External surface 544.7 m²
Inner volume 125.0 dm³
Fin materialAluminium
Net weight 1,406 kg
Fans
Quantity 12
Diameter 800 mm
Speed 900 rpm
Power 21,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 60.0 dB(A)
Sound power 92.0 dB(A)
Energy class E
Connections
Inlet 5"
Outlet 5"
Defrost
BC/BD-t-2X680GA5-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
406.222 kW Fluid flow 70.50 m³/h Pressure drop 43.0 kPa
Heat rejection · Low speed (Y)
335.718 kW Fluid flow 58.27 m³/h Pressure drop 30.7 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 222.79 not rated not rated not rated not rated not rated
40 406.22 225.34 not rated not rated not rated not rated
45 586.61 408.14 227.58 not rated not rated not rated
50 766.04 588.04 409.94 229.61 not rated not rated
55 945.11 767.04 589.46 411.67 231.54 not rated
60 1123.90 945.70 768.13 590.95 413.42 233.38

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 185.21 not rated not rated not rated not rated not rated
40 335.72 187.24 not rated not rated not rated not rated
45 483.24 337.08 189.05 not rated not rated not rated
50 629.89 484.09 338.34 190.66 not rated not rated
55 776.11 630.28 484.96 339.59 192.17 not rated
60 922.11 776.07 630.79 485.93 340.89 193.66

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 406.222 70.50 43.0
Low speed (Y) 335.718 58.27 30.7

Dimensions

Dimension drawing of BC/BD-t-2X680GA5-B01 C
Dimension drawing
Dimensions as drawn
A 6850 mm
B 1450 mm
C 2310 mm
F 1150 mm
G 550 mm
E 6400 mm
H 1050 mm
I 2260 mm
K 7350 mm
D IN 5"
D OUT 5"
Overall [mm]
Length 6850 mm
Width 2310 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.