Skip to Content

Dry cooler BC/BD-591EB1-B04 C

Dry cooler BC/BD-591EB1-B04 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-591EB1-B04 C

Heat rejection i
301.99 kW
Air flow
119,704 m³/h
Fans
5 × ⌀910 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 119,704 m³/h
External surface 720.7 m²
Inner volume 97.5 dm³
Fin materialAluminium
Net weight 895 kg
Fans
Quantity 5
Diameter 910 mm
Speed 840 rpm
Power 14,000 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 66.0 dB(A)
Sound power 98.0 dB(A)
Energy class E
Connections
Inlet 4"
Outlet 4"
Defrost
BC/BD-591EB1-B04 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
301.985 kW Fluid flow 52.41 m³/h Pressure drop 131.9 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
242.674 kW Fluid flow 42.12 m³/h Pressure drop 89.7 kPa above the recommended pressure drop

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 172.95 not rated not rated not rated not rated not rated
40 301.99 173.80 not rated not rated not rated not rated
45 428.66 302.35 174.60 not rated not rated not rated
50 554.58 428.57 302.77 175.38 not rated not rated
55 680.13 554.06 428.64 303.26 176.15 not rated
60 805.49 679.19 553.80 428.90 303.90 176.99

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 140.17 not rated not rated not rated not rated not rated
40 242.67 140.85 not rated not rated not rated not rated
45 343.05 242.95 141.48 not rated not rated not rated
50 442.73 342.96 243.27 142.10 not rated not rated
55 542.10 442.30 343.00 243.68 142.77 not rated
60 641.27 541.32 442.07 343.22 244.25 143.51

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 301.985 52.41 131.9
Low speed (Y) 242.674 42.12 89.7

Dimensions

Dimension drawing of BC/BD-591EB1-B04 C
Dimension drawing
Dimensions as drawn
A 7350 mm
B 1450 mm
C 1240 mm
F 1150 mm
G 550 mm
E 7100 mm
H 1400 mm
I 1190 mm
K 7650 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 7650 mm
Width 1240 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.