Skip to Content

Dry cooler BC/BD-663BB5-B19 C

Dry cooler BC/BD-663BB5-B19 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-663BB5-B19 C

Heat rejection i
156.80 kW
Air flow
71,025 m³/h
Fans
6 × ⌀630 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 71,025 m³/h
External surface 354.7 m²
Inner volume 62.4 dm³
Fin materialAluminium
Net weight 538 kg
Fans
Quantity 6
Diameter 630 mm
Speed 1,330 rpm
Power 7,500 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 60.0 dB(A)
Sound power 92.0 dB(A)
Energy class E
Connections
Inlet 4"
Outlet 4"
Defrost
BC/BD-663BB5-B19 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
156.802 kW Fluid flow 27.22 m³/h Pressure drop 14.0 kPa
Heat rejection · Low speed (Y)
134.891 kW Fluid flow 23.41 m³/h Pressure drop 10.7 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 85.15 not rated not rated not rated not rated not rated
40 156.80 86.30 not rated not rated not rated not rated
45 226.57 157.39 87.28 not rated not rated not rated
50 295.83 226.77 157.90 88.11 not rated not rated
55 364.84 295.69 226.96 158.37 88.86 not rated
60 433.74 364.38 295.59 227.18 158.86 89.57

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 73.42 not rated not rated not rated not rated not rated
40 134.89 74.47 not rated not rated not rated not rated
45 194.51 135.39 75.35 not rated not rated not rated
50 253.60 194.67 135.84 76.11 not rated not rated
55 312.47 253.45 194.82 136.26 76.78 not rated
60 371.21 312.05 253.36 195.02 136.70 77.42

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 156.802 27.22 14.0
Low speed (Y) 134.891 23.41 10.7

Dimensions

Dimension drawing of BC/BD-663BB5-B19 C
Dimension drawing
Dimensions as drawn
A 5850 mm
B 1220 mm
C 1230 mm
F 1050 mm
G 450 mm
E 5500 mm
H 900 mm
I 1180 mm
K 6200 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 5850 mm
Width 1230 mm
Height 1220 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.