BC/BD-2X363BC5-B01 C
156.82 kW
Defrost: None
Product code: BC/BD-t-2X263AC5-B19 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 44,139 m³/h |
|---|---|
| External surface | 311.2 m² |
| Inner volume | 59.7 dm³ |
| Fin material | Aluminium |
| Net weight | 367 kg |
| Quantity | 4 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 5,000 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 57.0 dB(A) |
|---|---|
| Sound power | 89.0 dB(A) |
| Energy class | E |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BC/BD-t-2X263AC5-B19 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 92.56 | not rated | not rated | not rated | not rated | not rated |
| 40 | 156.84 | 92.72 | not rated | not rated | not rated | not rated |
| 45 | 219.45 | 156.54 | 92.86 | not rated | not rated | not rated |
| 50 | 281.53 | 218.73 | 156.29 | 93.02 | not rated | not rated |
| 55 | 343.36 | 280.41 | 218.13 | 156.12 | 93.22 | not rated |
| 60 | 405.04 | 341.85 | 279.48 | 217.71 | 156.11 | 93.50 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 77.56 | not rated | not rated | not rated | not rated | not rated |
| 40 | 130.37 | 77.68 | not rated | not rated | not rated | not rated |
| 45 | 181.72 | 130.09 | 77.79 | not rated | not rated | not rated |
| 50 | 232.59 | 181.10 | 129.87 | 77.93 | not rated | not rated |
| 55 | 283.23 | 231.63 | 180.59 | 129.75 | 78.11 | not rated |
| 60 | 333.74 | 281.94 | 230.84 | 180.25 | 129.77 | 78.36 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 156.841 | 27.22 | 103.1 |
| Low speed (Y) | 130.365 | 22.61 | 74.3 |
| A | 2150 mm |
|---|---|
| B | 1220 mm |
| C | 2310 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 1900 mm |
| H | 900 mm |
| I | 2260 mm |
| K | 2400 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 2150 mm |
|---|---|
| Width | 2310 mm |
| Height | 1220 mm |