Skip to Content

Dry cooler BC/BD-663BD1-B19 C

Dry cooler BC/BD-663BD1-B19 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-663BD1-B19 C

Heat rejection i
231.53 kW
Air flow
65,150 m³/h
Fans
6 × ⌀630 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 65,150 m³/h
External surface 697.9 m²
Inner volume 88.8 dm³
Fin materialAluminium
Net weight 621 kg
Fans
Quantity 6
Diameter 630 mm
Speed 1,330 rpm
Power 7,500 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 59.0 dB(A)
Sound power 91.0 dB(A)
Energy class E
Connections
Inlet 4"
Outlet 4"
Defrost
BC/BD-663BD1-B19 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
231.534 kW Fluid flow 40.18 m³/h Pressure drop 74.1 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
190.703 kW Fluid flow 33.07 m³/h Pressure drop 52.5 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 136.66 not rated not rated not rated not rated not rated
40 231.53 136.96 not rated not rated not rated not rated
45 323.89 231.18 137.24 not rated not rated not rated
50 415.45 322.94 230.90 137.53 not rated not rated
55 506.64 413.96 322.19 230.74 137.89 not rated
60 597.62 504.60 412.73 321.69 230.82 138.36

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 113.37 not rated not rated not rated not rated not rated
40 190.70 113.73 not rated not rated not rated not rated
45 265.86 190.56 114.02 not rated not rated not rated
50 340.29 265.30 190.43 114.26 not rated not rated
55 414.38 339.35 264.82 190.32 114.57 not rated
60 488.29 413.08 338.54 264.40 190.39 114.98

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 231.534 40.18 74.1
Low speed (Y) 190.703 33.07 52.5

Dimensions

Dimension drawing of BC/BD-663BD1-B19 C
Dimension drawing
Dimensions as drawn
A 5850 mm
B 1220 mm
C 1230 mm
F 1050 mm
G 450 mm
E 5500 mm
H 900 mm
I 1180 mm
K 6200 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 5850 mm
Width 1230 mm
Height 1220 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.