BC/BD-2x380NB5-B03 C
230.69 kW
Defrost: None
Product code: BC/BD-391BC1-B04 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 73,185 m³/h |
|---|---|
| External surface | 720.7 m² |
| Inner volume | 88.0 dm³ |
| Fin material | Aluminium |
| Net weight | 675 kg |
| Quantity | 3 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 8,400 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 64.0 dB(A) |
|---|---|
| Sound power | 96.0 dB(A) |
| Energy class | E |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BC/BD-391BC1-B04 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 132.24 | not rated | not rated | not rated | not rated | not rated |
| 40 | 231.02 | 133.04 | not rated | not rated | not rated | not rated |
| 45 | 327.35 | 231.21 | 133.77 | not rated | not rated | not rated |
| 50 | 422.86 | 327.00 | 231.42 | 134.44 | not rated | not rated |
| 55 | 517.99 | 422.00 | 326.76 | 231.71 | 135.12 | not rated |
| 60 | 612.91 | 516.65 | 421.36 | 326.74 | 232.15 | 135.86 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 104.68 | not rated | not rated | not rated | not rated | not rated |
| 40 | 180.95 | 105.31 | not rated | not rated | not rated | not rated |
| 45 | 255.00 | 181.05 | 105.87 | not rated | not rated | not rated |
| 50 | 328.30 | 254.63 | 181.17 | 106.40 | not rated | not rated |
| 55 | 401.29 | 327.56 | 254.42 | 181.40 | 106.97 | not rated |
| 60 | 474.07 | 400.15 | 327.02 | 254.40 | 181.75 | 107.60 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 231.020 | 40.09 | 44.7 |
| Low speed (Y) | 180.950 | 31.40 | 28.8 |
| A | 5600 mm |
|---|---|
| B | 1450 mm |
| C | 1240 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 5350 mm |
| H | 1750 mm |
| I | 1190 mm |
| K | 5900 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 5900 mm |
|---|---|
| Width | 1240 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.