Skip to Content

Dry cooler BC/BD-680CB1-B03 C

Dry cooler BC/BD-680CB1-B03 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-680CB1-B03 C

Heat rejection i
210.26 kW
Air flow
59,520 m³/h
Fans
6 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 59,520 m³/h
External surface 1,081.1 m²
Inner volume 134.7 dm³
Fin materialAluminium
Net weight 1,144 kg
Fans
Quantity 6
Diameter 800 mm
Speed 435 rpm
Power 1,900 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 12
Acoustic
Sound pressure 39.0 dB(A)
Sound power 72.0 dB(A)
Energy class B
Connections
Inlet 4"
Outlet 4"
Defrost
BC/BD-680CB1-B03 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
210.261 kW Fluid flow 36.50 m³/h Pressure drop 17.0 kPa
Heat rejection · Low speed (Y)
165.222 kW Fluid flow 28.66 m³/h Pressure drop 11.0 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 121.78 not rated not rated not rated not rated not rated
40 210.26 122.36 not rated not rated not rated not rated
45 295.98 210.03 122.85 not rated not rated not rated
50 380.86 295.09 209.84 123.30 not rated not rated
55 465.32 379.35 294.36 209.73 123.76 not rated
60 549.55 463.22 378.09 293.83 209.81 124.30

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 96.54 not rated not rated not rated not rated not rated
40 165.22 97.06 not rated not rated not rated not rated
45 231.52 165.10 97.52 not rated not rated not rated
50 297.03 230.91 165.04 97.96 not rated not rated
55 362.18 295.97 230.44 165.10 98.44 not rated
60 427.13 360.69 295.14 230.20 165.33 98.99

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 210.261 36.50 17.0
Low speed (Y) 165.222 28.66 11.0

Dimensions

Dimension drawing of BC/BD-680CB1-B03 C
Dimension drawing
Dimensions as drawn
A 10850 mm
B 1450 mm
C 1240 mm
F 1150 mm
G 550 mm
E 10600 mm
H 1750 mm
I 1190 mm
K 11150 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 11150 mm
Width 1240 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.