BC/BD-2x480HC5-B03 C
210.80 kW
Defrost: None
Product code: BC/BD-t-763AC5-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 56,496 m³/h |
|---|---|
| External surface | 551.7 m² |
| Inner volume | 84.4 dm³ |
| Fin material | Aluminium |
| Net weight | 664 kg |
| Quantity | 7 |
|---|---|
| Diameter | 630 mm |
| Speed | 860 rpm |
| Power | 4,200 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 51.0 dB(A) |
|---|---|
| Sound power | 82.7 dB(A) |
| Energy class | D |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BC/BD-t-763AC5-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 121.05 | not rated | not rated | not rated | not rated | not rated |
| 40 | 210.73 | 122.03 | not rated | not rated | not rated | not rated |
| 45 | 297.03 | 210.81 | 122.87 | not rated | not rated | not rated |
| 50 | 382.22 | 296.43 | 210.90 | 123.63 | not rated | not rated |
| 55 | 466.89 | 381.01 | 295.98 | 211.11 | 124.39 | not rated |
| 60 | 551.27 | 465.11 | 380.07 | 295.77 | 211.48 | 125.21 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 210.734 | 36.55 | 14.7 |
| A | 6750 mm |
|---|---|
| B | 1220 mm |
| C | 1230 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 6400 mm |
| H | 900 mm |
| I | 1180 mm |
| K | 7100 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 6750 mm |
|---|---|
| Width | 1230 mm |
| Height | 1220 mm |
Our engineers answer with a selection for your conditions.