BC/BD-780EC5-B01 C
392.18 kW
Defrost: None
Product code: BC/BD-680CD5-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
How to read the code of this model.
| Air flow | 111,412 m³/h |
|---|---|
| External surface | 1,523.5 m² |
| Inner volume | 221.2 dm³ |
| Fin material | Aluminium |
| Net weight | 1,326 kg |
| Quantity | 6 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 10,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 88.5 dB(A) |
| Energy class | D |
| Inlet | 5" |
|---|---|
| Outlet | 5" |
| BC/BD-680CD5-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 227.01 | not rated | not rated | not rated | not rated | not rated |
| 40 | 392.14 | 228.32 | not rated | not rated | not rated | not rated |
| 45 | 552.26 | 392.16 | 229.44 | not rated | not rated | not rated |
| 50 | 710.82 | 551.26 | 392.27 | 230.52 | not rated | not rated |
| 55 | 868.64 | 708.87 | 550.53 | 392.58 | 231.66 | not rated |
| 60 | 1026.01 | 865.75 | 707.35 | 550.20 | 393.15 | 232.92 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 178.01 | not rated | not rated | not rated | not rated | not rated |
| 40 | 304.30 | 178.91 | not rated | not rated | not rated | not rated |
| 45 | 426.26 | 304.03 | 179.69 | not rated | not rated | not rated |
| 50 | 546.79 | 425.08 | 303.87 | 180.44 | not rated | not rated |
| 55 | 666.66 | 544.77 | 424.16 | 303.90 | 181.25 | not rated |
| 60 | 786.15 | 663.84 | 543.17 | 423.62 | 304.22 | 182.19 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 392.138 | 68.05 | 21.2 |
| Low speed (Y) | 304.300 | 52.78 | 13.4 |
| A | 11050 mm |
|---|---|
| B | 1450 mm |
| C | 1240 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 10600 mm |
| H | 1750 mm |
| I | 1190 mm |
| K | 11550 mm |
| D IN | 5" |
| D OUT | 5" |
| Length | 11550 mm |
|---|---|
| Width | 1240 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.