Skip to Content

Dry cooler BC/BD-780EC5-B01 C

Dry cooler BC/BD-780EC5-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-780EC5-B01 C

Heat rejection i
392.18 kW
Air flow
119,103 m³/h
Fans
7 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 119,103 m³/h
External surface 1,081.9 m²
Inner volume 252.9 dm³
Fin materialAluminium
Net weight 1,289 kg
Fans
Quantity 7
Diameter 800 mm
Speed 900 rpm
Power 12,600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 57.0 dB(A)
Sound power 89.5 dB(A)
Energy class E
Connections
Inlet 5"
Outlet 5"
Defrost
BC/BD-780EC5-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
392.184 kW Fluid flow 68.06 m³/h Pressure drop 61.4 kPa
Heat rejection · Low speed (Y)
306.887 kW Fluid flow 53.26 m³/h Pressure drop 39.7 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 230.02 not rated not rated not rated not rated not rated
40 392.18 230.76 not rated not rated not rated not rated
45 550.60 392.10 231.48 not rated not rated not rated
50 707.75 549.77 392.17 232.21 not rated not rated
55 864.30 706.22 549.24 392.44 233.04 not rated
60 1020.56 862.12 705.14 549.12 393.04 234.06

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 181.71 not rated not rated not rated not rated not rated
40 306.89 182.19 not rated not rated not rated not rated
45 428.81 306.62 182.64 not rated not rated not rated
50 549.70 427.89 306.46 183.14 not rated not rated
55 670.09 548.17 427.25 306.54 183.75 not rated
60 790.20 667.96 547.02 426.95 306.91 184.52

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 392.184 68.06 61.4
Low speed (Y) 306.887 53.26 39.7

Dimensions

Dimension drawing of BC/BD-780EC5-B01 C
Dimension drawing
Dimensions as drawn
A 10350 mm
B 1450 mm
C 1240 mm
F 1150 mm
G 550 mm
E 9900 mm
H 1400 mm
I 1190 mm
K 10850 mm
D IN 5"
D OUT 5"
Overall [mm]
Length 8750 mm
Width 1240 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.