BC/BD-2X480HB1-B01 C
320.09 kW
Defrost: None
Product code: BC/BD-680EC5-B01I C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 96,447 m³/h |
|---|---|
| External surface | 927.4 m² |
| Inner volume | 209.8 dm³ |
| Fin material | Aluminium |
| Net weight | 1,112 kg |
| Quantity | 6 |
|---|---|
| Diameter | 800 mm |
| Speed | 880 rpm |
| Power | 11,700 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 58.0 dB(A) |
|---|---|
| Sound power | 90.9 dB(A) |
| Energy class | E |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BC/BD-680EC5-B01I C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 186.57 | not rated | not rated | not rated | not rated | not rated |
| 40 | 319.95 | 187.29 | not rated | not rated | not rated | not rated |
| 45 | 450.08 | 319.90 | 187.96 | not rated | not rated | not rated |
| 50 | 579.12 | 449.34 | 319.94 | 188.62 | not rated | not rated |
| 55 | 707.66 | 577.73 | 448.82 | 320.13 | 189.34 | not rated |
| 60 | 835.87 | 705.60 | 576.67 | 448.61 | 320.59 | 190.19 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 319.950 | 55.53 | 40.2 |
| A | 8750 mm |
|---|---|
| B | 1450 mm |
| C | 1240 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 8500 mm |
| H | 1400 mm |
| I | 1190 mm |
| K | 9050 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 8750 mm |
|---|---|
| Width | 1240 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.