Dry cooler BC/BD-t-763AD1-B19 C

Dry cooler BC/BD-t-763AD1-B19 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-t-763AD1-B19 C

Heat rejection i
319.44 kW
Air flow
73,011 m³/h
Fans
7 × ⌀630 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Model nomenclature

How to read the code of this model.

  • A
    Series: BC/BD — BC = vertical, BD = horizontal dry cooler (air flow bottom to top).
  • B
    Fin type (optional "t"): t — t: louvered fins (high-efficiency fin surface)
  • D
    Number of fans per row: 7 — Digit 1-9; total fans = fan rows x this digit.
  • E
    Fan diameter: 63 — Ø630 mm
  • G
    Coil tube rows (2nd dimensional letter): D — 5 tube rows
  • H
    Fin spacing: 1 — 2.1 mm
  • I
    Generation code: B — generation B
  • J
    Fan data (fan motor code): 19 — three-phase 400 V 50 Hz, 4-pole AC fan (in this series)

Data

Coil
Air flow 73,011 m³/h
External surface 814.2 m²
Inner volume 99.8 dm³
Fin materialAluminium
Net weight 717 kg
Fans
Quantity 7
Diameter 630 mm
Speed 1,330 rpm
Power 8,800 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 59.0 dB(A)
Sound power 91.5 dB(A)
Energy class E
Connections
Inlet 4"
Outlet 4"
Defrost
BC/BD-t-763AD1-B19 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
319.441 kW Fluid flow 55.41 m³/h Pressure drop 124.6 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
250.503 kW Fluid flow 43.45 m³/h Pressure drop 81.0 kPa above the recommended pressure drop

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 195.67 not rated not rated not rated not rated not rated
40 319.44 195.47 not rated not rated not rated not rated
45 439.26 318.12 195.33 not rated not rated not rated
50 557.78 436.96 317.06 195.25 not rated not rated
55 675.69 554.54 435.08 316.23 195.39 not rated
60 793.27 671.55 551.90 433.59 315.84 195.80

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 155.16 not rated not rated not rated not rated not rated
40 250.50 155.24 not rated not rated not rated not rated
45 342.65 249.87 155.23 not rated not rated not rated
50 433.76 341.44 249.23 155.55 not rated not rated
55 524.40 432.02 340.27 249.23 156.08 not rated
60 614.78 522.15 430.36 340.04 249.65 156.88

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 319.441 55.41 124.6
Low speed (Y) 250.503 43.45 81.0

Dimensions

Dimension drawing of BC/BD-t-763AD1-B19 C
Dimension drawing
Dimensions as drawn
A 6750 mm
B 1220 mm
C 1230 mm
F 1050 mm
G 450 mm
E 6400 mm
H 900 mm
I 1180 mm
K 7100 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 6750 mm
Width 1230 mm
Height 1220 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.