Skip to Content

Dry cooler BC/BD-680FD1-B01 C

Dry cooler BC/BD-680FD1-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-680FD1-B01 C

Heat rejection i
422.69 kW
Air flow
103,237 m³/h
Fans
6 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 103,237 m³/h
External surface 1,710.3 m²
Inner volume 314.9 dm³
Fin materialAluminium
Net weight 1,410 kg
Fans
Quantity 6
Diameter 800 mm
Speed 900 rpm
Power 10,800 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 56.0 dB(A)
Sound power 89.0 dB(A)
Energy class D
Connections
Inlet 4"
Outlet 4"
Defrost
BC/BD-680FD1-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
422.685 kW Fluid flow 73.30 m³/h Pressure drop 57.1 kPa
Heat rejection · Low speed (Y)
319.834 kW Fluid flow 55.48 m³/h Pressure drop 34.7 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 255.27 not rated not rated not rated not rated not rated
40 422.69 255.43 not rated not rated not rated not rated
45 585.18 421.57 255.63 not rated not rated not rated
50 746.02 582.95 420.74 255.94 not rated not rated
55 906.09 742.73 581.20 420.31 256.50 not rated
60 1065.74 901.77 740.12 580.10 420.40 257.37

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 195.37 not rated not rated not rated not rated not rated
40 319.83 195.34 not rated not rated not rated not rated
45 440.34 318.75 195.36 not rated not rated not rated
50 559.54 438.34 317.91 195.50 not rated not rated
55 678.13 556.68 436.76 317.42 195.84 not rated
60 796.40 674.45 554.40 435.72 317.36 196.48

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 422.685 73.30 57.1
Low speed (Y) 319.834 55.48 34.7

Dimensions

Dimension drawing of BC/BD-680FD1-B01 C
Dimension drawing
Dimensions as drawn
A 10850 mm
B 1450 mm
C 1240 mm
F 1150 mm
G 550 mm
E 10600 mm
H 1750 mm
I 1190 mm
K 11150 mm
D IN 4"
D OUT 4"
Overall [mm]
Length 11150 mm
Width 1240 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.