Skip to Content

Dry cooler BC/BD-780AB5-B03 C

Dry cooler BC/BD-780AB5-B03 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-780AB5-B03 C

Heat rejection i
194.76 kW
Air flow
63,060 m³/h
Fans
7 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Model nomenclature

How to read the code of this model.

  • A
    Series: BC/BD — BC = vertical, BD = horizontal dry cooler (air flow bottom to top).
  • D
    Number of fans per row: 7 — Digit 1-9; total fans = fan rows x this digit.
  • E
    Fan diameter: 80 — Ø800 mm
  • G
    Coil tube rows (2nd dimensional letter): B — 3 tube rows
  • H
    Fin spacing: 5 — 2.5 mm
  • I
    Generation code: B — generation B
  • J
    Fan data (fan motor code): 03 — three-phase 400 V 50 Hz, 12-pole AC fan (in this series)

Data

Coil
Air flow 63,060 m³/h
External surface 731.3 m²
Inner volume 102.9 dm³
Fin materialAluminium
Net weight 1,061 kg
Fans
Quantity 7
Diameter 800 mm
Speed 435 rpm
Power 2,200 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 12
Acoustic
Sound pressure 40.0 dB(A)
Sound power 72.5 dB(A)
Energy class C
Connections
Inlet 3"
Outlet 3"
Defrost
BC/BD-780AB5-B03 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
194.763 kW Fluid flow 33.80 m³/h Pressure drop 76.4 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
155.059 kW Fluid flow 26.91 m³/h Pressure drop 51.0 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 114.11 not rated not rated not rated not rated not rated
40 194.76 114.45 not rated not rated not rated not rated
45 273.67 194.74 114.77 not rated not rated not rated
50 351.99 273.30 194.76 115.11 not rated not rated
55 430.05 351.29 273.05 194.89 115.49 not rated
60 507.96 429.04 350.80 272.99 195.15 115.96

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 91.58 not rated not rated not rated not rated not rated
40 155.06 91.82 not rated not rated not rated not rated
45 217.00 154.95 92.02 not rated not rated not rated
50 278.44 216.59 154.87 92.25 not rated not rated
55 339.64 277.74 216.26 154.89 92.53 not rated
60 400.71 338.65 277.15 216.07 155.03 92.87

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 194.763 33.80 76.4
Low speed (Y) 155.059 26.91 51.0

Dimensions

Dimension drawing of BC/BD-780AB5-B03 C
Dimension drawing
Dimensions as drawn
A 8750 mm
B 1450 mm
C 1240 mm
F 1150 mm
G 550 mm
E 8500 mm
H 1200 mm
I 1190 mm
K 9050 mm
D IN 3"
D OUT 3"
Overall [mm]
Length 9050 mm
Width 1240 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.