BC/BD-580FC1-B03 C
195.06 kW
Defrost: None
Product code: BC/BD-t-563AC5-B19 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 55,374 m³/h |
|---|---|
| External surface | 394.1 m² |
| Inner volume | 57.4 dm³ |
| Fin material | Aluminium |
| Net weight | 483 kg |
| Quantity | 5 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 6,300 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 58.0 dB(A) |
|---|---|
| Sound power | 90.0 dB(A) |
| Energy class | E |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BC/BD-t-563AC5-B19 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 113.89 | not rated | not rated | not rated | not rated | not rated |
| 40 | 194.93 | 114.25 | not rated | not rated | not rated | not rated |
| 45 | 273.74 | 194.67 | 114.57 | not rated | not rated | not rated |
| 50 | 351.84 | 272.93 | 194.46 | 114.89 | not rated | not rated |
| 55 | 429.61 | 350.51 | 272.26 | 194.37 | 115.24 | not rated |
| 60 | 507.17 | 427.77 | 349.41 | 271.80 | 194.40 | 115.67 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 95.52 | not rated | not rated | not rated | not rated | not rated |
| 40 | 162.18 | 95.81 | not rated | not rated | not rated | not rated |
| 45 | 226.87 | 161.93 | 96.08 | not rated | not rated | not rated |
| 50 | 290.89 | 226.15 | 161.74 | 96.34 | not rated | not rated |
| 55 | 354.61 | 289.75 | 225.58 | 161.66 | 96.65 | not rated |
| 60 | 418.15 | 353.04 | 288.81 | 225.20 | 161.73 | 97.04 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 194.928 | 33.83 | 59.6 |
| Low speed (Y) | 162.181 | 28.13 | 42.9 |
| A | 4850 mm |
|---|---|
| B | 1220 mm |
| C | 1230 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 4600 mm |
| H | 900 mm |
| I | 1180 mm |
| K | 5100 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 4850 mm |
|---|---|
| Width | 1230 mm |
| Height | 1220 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.