BC/BD-563CD1-B19 C
195.12 kW
Defrost: None
Product code: BC/BD-580FC1-B03 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 45,203 m³/h |
|---|---|
| External surface | 1,140.2 m² |
| Inner volume | 204.6 dm³ |
| Fin material | Aluminium |
| Net weight | 1,072 kg |
| Quantity | 5 |
|---|---|
| Diameter | 800 mm |
| Speed | 435 rpm |
| Power | 1,600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 12 |
| Sound pressure | 38.0 dB(A) |
|---|---|
| Sound power | 71.0 dB(A) |
| Energy class | B |
| Inlet | 2 1/2" |
|---|---|
| Outlet | 2 1/2" |
| BC/BD-580FC1-B03 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 120.57 | not rated | not rated | not rated | not rated | not rated |
| 40 | 195.06 | 120.30 | not rated | not rated | not rated | not rated |
| 45 | 267.56 | 194.22 | 120.09 | not rated | not rated | not rated |
| 50 | 339.40 | 266.20 | 193.56 | 119.99 | not rated | not rated |
| 55 | 410.95 | 337.54 | 265.11 | 193.11 | 120.03 | not rated |
| 60 | 482.33 | 408.60 | 336.04 | 264.35 | 192.94 | 120.26 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 92.09 | not rated | not rated | not rated | not rated | not rated |
| 40 | 147.53 | 91.81 | not rated | not rated | not rated | not rated |
| 45 | 201.43 | 146.79 | 91.59 | not rated | not rated | not rated |
| 50 | 254.84 | 200.27 | 146.18 | 91.46 | not rated | not rated |
| 55 | 308.02 | 253.27 | 199.31 | 145.76 | 91.45 | not rated |
| 60 | 361.08 | 306.06 | 251.98 | 198.63 | 145.57 | 91.60 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 195.061 | 33.83 | 114.8 |
| Low speed (Y) | 147.529 | 25.59 | 69.9 |
| A | 9100 mm |
|---|---|
| B | 1450 mm |
| C | 1240 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 8850 mm |
| H | 1750 mm |
| I | 1190 mm |
| K | 9400 mm |
| D IN | 2 1/2" |
| D OUT | 2 1/2" |
| Length | 9400 mm |
|---|---|
| Width | 1240 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.