BC/BD-580FC1-B03 C
195.06 kW
Defrost: None
Product code: BC/BD-563CD1-B19 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 53,799 m³/h |
|---|---|
| External surface | 772.2 m² |
| Inner volume | 93.3 dm³ |
| Fin material | Aluminium |
| Net weight | 608 kg |
| Quantity | 5 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 6,300 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 58.0 dB(A) |
|---|---|
| Sound power | 90.0 dB(A) |
| Energy class | E |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BC/BD-563CD1-B19 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 112.15 | not rated | not rated | not rated | not rated | not rated |
| 40 | 195.12 | 112.89 | not rated | not rated | not rated | not rated |
| 45 | 275.30 | 195.09 | 113.52 | not rated | not rated | not rated |
| 50 | 354.59 | 274.66 | 195.06 | 114.11 | not rated | not rated |
| 55 | 433.46 | 353.38 | 274.15 | 195.17 | 114.70 | not rated |
| 60 | 512.08 | 431.72 | 352.42 | 273.86 | 195.42 | 115.37 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 92.95 | not rated | not rated | not rated | not rated | not rated |
| 40 | 160.29 | 93.66 | not rated | not rated | not rated | not rated |
| 45 | 225.14 | 160.43 | 94.29 | not rated | not rated | not rated |
| 50 | 289.15 | 224.84 | 160.59 | 94.88 | not rated | not rated |
| 55 | 352.77 | 288.47 | 224.66 | 160.83 | 95.48 | not rated |
| 60 | 416.18 | 351.73 | 287.98 | 224.65 | 161.21 | 96.06 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 195.121 | 33.87 | 21.8 |
| Low speed (Y) | 160.287 | 27.80 | 15.2 |
| A | 4800 mm |
|---|---|
| B | 1200 mm |
| C | 1240 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 4600 mm |
| H | 900 mm |
| I | 1190 mm |
| K | 5100 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 5100 mm |
|---|---|
| Width | 1240 mm |
| Height | 1200 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.