BC/BD-563CD1-B19 C
195.12 kW
Defrost: None
Product code: BC/BD-780DB5-B03 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 59,717 m³/h |
|---|---|
| External surface | 695.5 m² |
| Inner volume | 153.6 dm³ |
| Fin material | Aluminium |
| Net weight | 1,081 kg |
| Quantity | 7 |
|---|---|
| Diameter | 800 mm |
| Speed | 435 rpm |
| Power | 2,200 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 12 |
| Sound pressure | 40.0 dB(A) |
|---|---|
| Sound power | 72.5 dB(A) |
| Energy class | C |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BC/BD-780DB5-B03 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 113.78 | not rated | not rated | not rated | not rated | not rated |
| 40 | 195.20 | 114.29 | not rated | not rated | not rated | not rated |
| 45 | 274.63 | 195.29 | 114.77 | not rated | not rated | not rated |
| 50 | 353.40 | 274.36 | 195.44 | 115.26 | not rated | not rated |
| 55 | 431.87 | 352.79 | 274.21 | 195.69 | 115.77 | not rated |
| 60 | 510.17 | 430.93 | 352.38 | 274.27 | 196.08 | 116.37 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 90.14 | not rated | not rated | not rated | not rated | not rated |
| 40 | 153.37 | 90.52 | not rated | not rated | not rated | not rated |
| 45 | 214.84 | 153.36 | 90.87 | not rated | not rated | not rated |
| 50 | 275.75 | 214.51 | 153.40 | 91.23 | not rated | not rated |
| 55 | 336.42 | 275.13 | 214.31 | 153.53 | 91.63 | not rated |
| 60 | 396.92 | 335.50 | 274.70 | 214.28 | 153.82 | 92.10 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 195.204 | 33.88 | 30.4 |
| Low speed (Y) | 153.370 | 26.62 | 19.7 |
| A | 8750 mm |
|---|---|
| B | 1450 mm |
| C | 1240 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 8500 mm |
| H | 1200 mm |
| I | 1190 mm |
| K | 9050 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 9050 mm |
|---|---|
| Width | 1240 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.