Skip to Content

Dry cooler BC/BD-t-163AA1-B19 C

Dry cooler BC/BD-t-163AA1-B19 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-t-163AA1-B19 C

Heat rejection i
28.86 kW
Air flow
11,935 m³/h
Fans
1 × ⌀630 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 11,935 m³/h
External surface 46.5 m²
Inner volume 7.1 dm³
Fin materialAluminium
Net weight 119 kg
Fans
Quantity 1
Diameter 630 mm
Speed 1,330 rpm
Power 1,300 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 53.0 dB(A)
Sound power 84.0 dB(A)
Energy class E
Connections
Inlet 1 1/4"
Outlet 1 1/4"
Defrost
BC/BD-t-163AA1-B19 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
28.864 kW Fluid flow 5.01 m³/h Pressure drop 76.9 kPa above the recommended pressure drop
Heat rejection · Low speed (Y)
24.964 kW Fluid flow 4.33 m³/h Pressure drop 59.5 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 16.20 not rated not rated not rated not rated not rated
40 28.86 16.31 not rated not rated not rated not rated
45 41.28 28.90 16.41 not rated not rated not rated
50 53.62 41.26 28.94 16.50 not rated not rated
55 65.92 53.53 41.24 28.97 16.58 not rated
60 78.21 65.78 53.46 41.23 29.02 16.66

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 14.09 not rated not rated not rated not rated not rated
40 24.96 14.18 not rated not rated not rated not rated
45 35.61 24.99 14.27 not rated not rated not rated
50 46.18 35.58 25.02 14.34 not rated not rated
55 56.72 46.10 35.56 25.05 14.41 not rated
60 67.24 56.58 46.03 35.56 25.10 14.49

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 28.864 5.01 76.9
Low speed (Y) 24.964 4.33 59.5

Dimensions

Dimension drawing of BC/BD-t-163AA1-B19 C
Dimension drawing
Dimensions as drawn
A 1250 mm
B 1220 mm
C 1230 mm
F 1050 mm
G 450 mm
E 1000 mm
H 900 mm
I 1180 mm
K 1500 mm
D IN 1 1/4"
D OUT 1 1/4"
Overall [mm]
Length 1250 mm
Width 1230 mm
Height 1220 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.