BC/BD-2X163BD1-B01 C
59.81 kW
Defrost: None
Product code: BC/BD-t-191OB5-B04 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 23,653 m³/h |
|---|---|
| External surface | 92.0 m² |
| Inner volume | 13.9 dm³ |
| Fin material | Aluminium |
| Net weight | 203 kg |
| Quantity | 1 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 2,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 60.0 dB(A) |
|---|---|
| Sound power | 91.2 dB(A) |
| Energy class | E |
| Inlet | 1 1/2" |
|---|---|
| Outlet | 1 1/2" |
| BC/BD-t-191OB5-B04 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 32.96 | not rated | not rated | not rated | not rated | not rated |
| 40 | 59.88 | 33.35 | not rated | not rated | not rated | not rated |
| 45 | 86.19 | 60.11 | 33.68 | not rated | not rated | not rated |
| 50 | 112.29 | 86.29 | 60.32 | 33.98 | not rated | not rated |
| 55 | 138.32 | 112.29 | 86.40 | 60.53 | 34.27 | not rated |
| 60 | 164.29 | 138.20 | 112.31 | 86.53 | 60.75 | 34.55 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | not rated | not rated | not rated | not rated | not rated | not rated |
| 40 | not rated | 26.82 | not rated | not rated | not rated | not rated |
| 45 | not rated | 47.93 | 27.09 | not rated | not rated | not rated |
| 50 | not rated | 68.48 | 48.09 | 27.35 | not rated | not rated |
| 55 | not rated | 88.86 | 68.56 | 48.28 | 27.59 | not rated |
| 60 | not rated | 109.16 | 88.87 | 68.70 | 48.47 | 27.83 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 59.882 | 10.39 | 36.3 |
| Low speed (Y) | — | — | — |
| A | 1750 mm |
|---|---|
| B | 1450 mm |
| C | 1230 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 1500 mm |
| H | 1400 mm |
| I | 1180 mm |
| K | 2050 mm |
| D IN | 1 1/2" |
| D OUT | 1 1/2" |
| Length | 2050 mm |
|---|---|
| Width | 1230 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.