BC/BD-2X350CA1-B09 C
80.20 kW
Defrost: None
Product code: BC/BD-t-191PC5-B04 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 24,100 m³/h |
|---|---|
| External surface | 153.3 m² |
| Inner volume | 22.9 dm³ |
| Fin material | Aluminium |
| Net weight | 234 kg |
| Quantity | 1 |
|---|---|
| Diameter | 910 mm |
| Speed | 840 rpm |
| Power | 2,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 59.0 dB(A) |
|---|---|
| Sound power | 91.0 dB(A) |
| Energy class | E |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| BC/BD-t-191PC5-B04 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 45.89 | not rated | not rated | not rated | not rated | not rated |
| 40 | 80.18 | 46.21 | not rated | not rated | not rated | not rated |
| 45 | 113.49 | 80.24 | 46.48 | not rated | not rated | not rated |
| 50 | 146.48 | 113.34 | 80.32 | 46.74 | not rated | not rated |
| 55 | 179.31 | 146.15 | 113.25 | 80.42 | 47.00 | not rated |
| 60 | 212.07 | 178.80 | 145.89 | 113.23 | 80.58 | 47.28 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 35.95 | not rated | not rated | not rated | not rated | not rated |
| 40 | 62.14 | 36.19 | not rated | not rated | not rated | not rated |
| 45 | 87.44 | 62.16 | 36.41 | not rated | not rated | not rated |
| 50 | 112.47 | 87.31 | 62.20 | 36.62 | not rated | not rated |
| 55 | 137.36 | 112.18 | 87.22 | 62.28 | 36.83 | not rated |
| 60 | 162.18 | 136.94 | 111.98 | 87.21 | 62.42 | 37.07 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 80.177 | 13.91 | 38.6 |
| Low speed (Y) | 62.136 | 10.79 | 24.5 |
| A | 2100 mm |
|---|---|
| B | 1450 mm |
| C | 1230 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 1850 mm |
| H | 1750 mm |
| I | 1180 mm |
| K | 2400 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 2400 mm |
|---|---|
| Width | 1230 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.