Skip to Content

Dry cooler BC/BD-280CD1-B03 C

Dry cooler BC/BD-280CD1-B03 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-280CD1-B03 C

Heat rejection i
80.34 kW
Air flow
18,093 m³/h
Fans
2 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 18,093 m³/h
External surface 600.3 m²
Inner volume 67.0 dm³
Fin materialAluminium
Net weight 480 kg
Fans
Quantity 2
Diameter 800 mm
Speed 435 rpm
Power 600 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 12
Acoustic
Sound pressure 35.0 dB(A)
Sound power 67.0 dB(A)
Energy class B
Connections
Inlet 2"
Outlet 2"
Defrost
BC/BD-280CD1-B03 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
80.342 kW Fluid flow 13.94 m³/h Pressure drop 62.5 kPa
Heat rejection · Low speed (Y)
60.479 kW Fluid flow 10.49 m³/h Pressure drop 37.7 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 49.72 not rated not rated not rated not rated not rated
40 80.34 49.62 not rated not rated not rated not rated
45 110.05 79.98 49.55 not rated not rated not rated
50 139.45 109.45 79.69 49.52 not rated not rated
55 168.72 138.63 108.96 79.49 49.55 not rated
60 197.91 167.68 137.96 108.62 79.42 49.66

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 37.82 not rated not rated not rated not rated not rated
40 60.48 37.72 not rated not rated not rated not rated
45 82.43 60.16 37.64 not rated not rated not rated
50 104.15 81.92 59.90 37.60 not rated not rated
55 125.78 103.47 81.50 59.72 37.60 not rated
60 147.35 124.92 102.91 81.20 59.63 37.67

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 80.342 13.94 62.5
Low speed (Y) 60.479 10.49 37.7

Dimensions

Dimension drawing of BC/BD-280CD1-B03 C
Dimension drawing
Dimensions as drawn
A 3850 mm
B 1450 mm
C 1240 mm
F 1150 mm
G 550 mm
E 3600 mm
H 1750 mm
I 1190 mm
K 4150 mm
D IN 2"
D OUT 2"
Overall [mm]
Length 4150 mm
Width 1240 mm
Height 1450 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.