BC/BD-280CD1-B03 C
80.34 kW
Defrost: None
Product code: BC/BD-2x180CD1-B03 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 18,093 m³/h |
|---|---|
| External surface | 600.3 m² |
| Inner volume | 72.0 dm³ |
| Fin material | Aluminium |
| Net weight | 475 kg |
| Quantity | 2 |
|---|---|
| Diameter | 800 mm |
| Speed | 435 rpm |
| Power | 600 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 12 |
| Sound pressure | 35.0 dB(A) |
|---|---|
| Sound power | 67.0 dB(A) |
| Energy class | B |
| Inlet | 2" |
|---|---|
| Outlet | 2" |
| BC/BD-2x180CD1-B03 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 49.76 | not rated | not rated | not rated | not rated | not rated |
| 40 | 80.38 | 49.66 | not rated | not rated | not rated | not rated |
| 45 | 110.08 | 80.01 | 49.59 | not rated | not rated | not rated |
| 50 | 139.48 | 109.48 | 79.72 | 49.56 | not rated | not rated |
| 55 | 168.75 | 138.66 | 108.99 | 79.52 | 49.58 | not rated |
| 60 | 197.94 | 167.71 | 137.99 | 108.65 | 79.45 | 49.69 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 37.85 | not rated | not rated | not rated | not rated | not rated |
| 40 | 60.50 | 37.75 | not rated | not rated | not rated | not rated |
| 45 | 82.45 | 60.18 | 37.67 | not rated | not rated | not rated |
| 50 | 104.17 | 81.94 | 59.92 | 37.62 | not rated | not rated |
| 55 | 125.80 | 103.48 | 81.52 | 59.73 | 37.62 | not rated |
| 60 | 147.37 | 124.94 | 102.92 | 81.22 | 59.65 | 37.69 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 80.377 | 13.94 | 68.5 |
| Low speed (Y) | 60.501 | 10.49 | 41.4 |
| A | 2100 mm |
|---|---|
| B | 1450 mm |
| C | 2360 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 1850 mm |
| H | 1750 mm |
| I | 2310 mm |
| K | 2400 mm |
| D IN | 2" |
| D OUT | 2" |
| Length | 2400 mm |
|---|---|
| Width | 2360 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.