BC/BD-280HD1-B03 C
57.57 kW
Defrost: None
Product code: BC/BD-t-263AA1-B19 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
How to read the code of this model.
| Air flow | 23,870 m³/h |
|---|---|
| External surface | 93.1 m² |
| Inner volume | 12.4 dm³ |
| Fin material | Aluminium |
| Net weight | 196 kg |
| Quantity | 2 |
|---|---|
| Diameter | 630 mm |
| Speed | 1,330 rpm |
| Power | 2,500 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 4 |
| Sound pressure | 55.0 dB(A) |
|---|---|
| Sound power | 87.0 dB(A) |
| Energy class | E |
| Inlet | 1 1/2" |
|---|---|
| Outlet | 1 1/2" |
| BC/BD-t-263AA1-B19 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 32.30 | not rated | not rated | not rated | not rated | not rated |
| 40 | 57.62 | 32.53 | not rated | not rated | not rated | not rated |
| 45 | 82.46 | 57.71 | 32.73 | not rated | not rated | not rated |
| 50 | 107.14 | 82.42 | 57.78 | 32.90 | not rated | not rated |
| 55 | 131.75 | 106.97 | 82.38 | 57.86 | 33.07 | not rated |
| 60 | 156.32 | 131.47 | 106.83 | 82.37 | 57.95 | 33.24 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 28.09 | not rated | not rated | not rated | not rated | not rated |
| 40 | 49.85 | 28.29 | not rated | not rated | not rated | not rated |
| 45 | 71.14 | 49.91 | 28.45 | not rated | not rated | not rated |
| 50 | 92.28 | 71.08 | 49.97 | 28.61 | not rated | not rated |
| 55 | 113.35 | 92.12 | 71.05 | 50.03 | 28.76 | not rated |
| 60 | 134.39 | 113.09 | 91.99 | 71.04 | 50.12 | 28.91 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 57.624 | 10.00 | 71.8 |
| Low speed (Y) | 49.845 | 8.65 | 55.5 |
| A | 2150 mm |
|---|---|
| B | 1220 mm |
| C | 1230 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 1900 mm |
| H | 900 mm |
| I | 1180 mm |
| K | 2400 mm |
| D IN | 1 1/2" |
| D OUT | 1 1/2" |
| Length | 2150 mm |
|---|---|
| Width | 1230 mm |
| Height | 1220 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.