BC/BD-t-2X363AC1-B01 C
196.99 kW
Defrost: None
Product code: BC/BD-t-2X363AD5-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 45,730 m³/h |
|---|---|
| External surface | 583.6 m² |
| Inner volume | 107.6 dm³ |
| Fin material | Aluminium |
| Net weight | 556 kg |
| Quantity | 6 |
|---|---|
| Diameter | 630 mm |
| Speed | 860 rpm |
| Power | 3,600 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 51.0 dB(A) |
|---|---|
| Sound power | 82.8 dB(A) |
| Energy class | D |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BC/BD-t-2X363AD5-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 120.01 | not rated | not rated | not rated | not rated | not rated |
| 40 | 197.31 | 120.08 | not rated | not rated | not rated | not rated |
| 45 | 272.01 | 196.70 | 120.17 | not rated | not rated | not rated |
| 50 | 345.87 | 270.83 | 196.23 | 120.32 | not rated | not rated |
| 55 | 419.32 | 344.14 | 269.89 | 195.97 | 120.59 | not rated |
| 60 | 492.56 | 417.08 | 342.77 | 269.28 | 195.97 | 121.02 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 197.310 | 34.22 | 48.7 |
| A | 3150 mm |
|---|---|
| B | 1220 mm |
| C | 2310 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 2800 mm |
| H | 900 mm |
| I | 2260 mm |
| K | 3500 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 3150 mm |
|---|---|
| Width | 2310 mm |
| Height | 1220 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.