BC/BD-2x380AC1-B03 C
190.51 kW
Defrost: None
Product code: BC/BD-t-2X463AA1-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 71,008 m³/h |
|---|---|
| External surface | 367.4 m² |
| Inner volume | 59.7 dm³ |
| Fin material | Aluminium |
| Net weight | 585 kg |
| Quantity | 8 |
|---|---|
| Diameter | 630 mm |
| Speed | 860 rpm |
| Power | 4,800 W |
| Supply | 230V/1Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 52.0 dB(A) |
|---|---|
| Sound power | 83.5 dB(A) |
| Energy class | D |
| Inlet | 3" |
|---|---|
| Outlet | 3" |
| BC/BD-t-2X463AA1-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 107.45 | not rated | not rated | not rated | not rated | not rated |
| 40 | 190.57 | 108.21 | not rated | not rated | not rated | not rated |
| 45 | 271.88 | 190.83 | 108.88 | not rated | not rated | not rated |
| 50 | 352.61 | 271.70 | 191.07 | 109.48 | not rated | not rated |
| 55 | 433.07 | 352.03 | 271.59 | 191.36 | 110.07 | not rated |
| 60 | 513.39 | 432.09 | 351.56 | 271.58 | 191.70 | 110.66 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| Single phase | 190.574 | 33.07 | 48.3 |
| A | 3950 mm |
|---|---|
| B | 1220 mm |
| C | 2310 mm |
| F | 1050 mm |
| G | 450 mm |
| E | 3700 mm |
| H | 900 mm |
| I | 2260 mm |
| K | 4200 mm |
| D IN | 3" |
| D OUT | 3" |
| Length | 3950 mm |
|---|---|
| Width | 2310 mm |
| Height | 1220 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.