Dry cooler BC/BD-t-2X480GC5-B01 C

Dry cooler BC/BD-t-2X480GC5-B01 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-t-2X480GC5-B01 C

Heat rejection i
396.54 kW
Air flow
119,127 m³/h
Fans
8 × ⌀800 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 119,127 m³/h
External surface 726.2 m²
Inner volume 145.6 dm³
Fin materialAluminium
Net weight 1,071 kg
Fans
Quantity 8
Diameter 800 mm
Speed 900 rpm
Power 14,400 W
Supply 400V/3Ph/50Hz
Motor type AC
Poles 6
Acoustic
Sound pressure 60.0 dB(A)
Sound power 91.9 dB(A)
Energy class E
Connections
Inlet 5"
Outlet 5"
Defrost
BC/BD-t-2X480GC5-B01 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · High speed (Δ)
396.538 kW Fluid flow 68.82 m³/h Pressure drop 55.4 kPa
Heat rejection · Low speed (Y)
307.828 kW Fluid flow 53.43 m³/h Pressure drop 35.4 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

High speed (Δ)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 229.46 not rated not rated not rated not rated not rated
40 396.54 230.94 not rated not rated not rated not rated
45 559.27 397.19 232.30 not rated not rated not rated
50 720.55 559.26 397.97 233.67 not rated not rated
55 881.12 719.94 559.53 398.92 235.08 not rated
60 1041.36 879.93 719.70 560.20 400.23 236.66

Low speed (Y)

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 180.06 not rated not rated not rated not rated not rated
40 307.83 181.21 not rated not rated not rated not rated
45 431.71 308.23 182.29 not rated not rated not rated
50 554.36 431.62 308.79 183.36 not rated not rated
55 676.42 553.78 431.79 309.56 184.53 not rated
60 798.15 675.39 553.63 432.35 310.62 185.99

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
High speed (Δ) 396.538 68.82 55.4
Low speed (Y) 307.828 53.43 35.4

Dimensions

Dimension drawing of BC/BD-t-2X480GC5-B01 C
Dimension drawing
Dimensions as drawn
A 4750 mm
B 1450 mm
C 2310 mm
F 1150 mm
G 550 mm
E 4300 mm
H 1050 mm
I 2260 mm
K 5250 mm
D IN 5"
D OUT 5"
Overall [mm]
Length 4750 mm
Width 2310 mm
Height 1450 mm

Downloads

Ask about product