BC/BD-2x580AB5-B01 C
395.12 kW
Defrost: None
Product code: BC/BD-t-2x380JB1-B01 C
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Air flow | 116,236 m³/h |
|---|---|
| External surface | 803.7 m² |
| Inner volume | 118.6 dm³ |
| Fin material | Aluminium |
| Net weight | 997 kg |
| Quantity | 6 |
|---|---|
| Diameter | 800 mm |
| Speed | 900 rpm |
| Power | 10,800 W |
| Supply | 400V/3Ph/50Hz |
| Motor type | AC |
| Poles | 6 |
| Sound pressure | 56.0 dB(A) |
|---|---|
| Sound power | 88.0 dB(A) |
| Energy class | D |
| Inlet | 4" |
|---|---|
| Outlet | 4" |
| BC/BD-t-2x380JB1-B01 C | None |
|---|
Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.
WATER 40 → 35 °C, air inlet 25 °C
WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.
≈ 1.23 estimate — vendor data irregular here
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 231.65 | not rated | not rated | not rated | not rated | not rated |
| 40 | 395.25 | 232.25 | not rated | not rated | not rated | not rated |
| 45 | 554.80 | 394.73 | 232.76 | not rated | not rated | not rated |
| 50 | 713.03 | 553.31 | 394.34 | 233.30 | not rated | not rated |
| 55 | 870.59 | 710.56 | 552.11 | 394.19 | 233.93 | not rated |
| 60 | 1027.85 | 867.24 | 708.57 | 551.27 | 394.36 | 234.75 |
| Fluid inlet [°C] \ air [°C] | 25 | 30 | 35 | 40 | 45 | 50 |
|---|---|---|---|---|---|---|
| 35 | 182.89 | not rated | not rated | not rated | not rated | not rated |
| 40 | 308.78 | 183.24 | not rated | not rated | not rated | not rated |
| 45 | 431.25 | 308.20 | 183.58 | not rated | not rated | not rated |
| 50 | 552.57 | 429.84 | 307.76 | 183.94 | not rated | not rated |
| 55 | 673.34 | 550.37 | 428.70 | 307.52 | 184.42 | not rated |
| 60 | 793.82 | 670.38 | 548.59 | 427.95 | 307.60 | 185.05 |
Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %
| Fan connection | Heat rejection [kW] | Fluid flow [m³/h] | Pressure drop [kPa] |
|---|---|---|---|
| High speed (Δ) | 395.251 | 68.60 | 114.8 |
| Low speed (Y) | 308.780 | 53.55 | 74.0 |
| A | 5600 mm |
|---|---|
| B | 1450 mm |
| C | 2310 mm |
| F | 1150 mm |
| G | 550 mm |
| E | 5350 mm |
| H | 1750 mm |
| I | 2260 mm |
| K | 5900 mm |
| D IN | 4" |
| D OUT | 4" |
| Length | 5900 mm |
|---|---|
| Width | 2310 mm |
| Height | 1450 mm |
Our engineers answer with a selection for your conditions.
The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.