Skip to Content

Dry cooler BC/BD-t-2X550AA5-B09 C

Dry cooler BC/BD-t-2X550AA5-B09 C
Illustrative photo

Producer: Karyer · Line: BC/BD (General)

Product code: BC/BD-t-2X550AA5-B09 C

Heat rejection i
159.86 kW
Air flow
72,664 m³/h
Fans
10 × ⌀500 mm

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Data

Coil
Air flow 72,664 m³/h
External surface 251.0 m²
Inner volume 46.7 dm³
Fin materialAluminium
Net weight 519 kg
Fans
Quantity 10
Diameter 500 mm
Speed 1,330 rpm
Power 7,100 W
Supply 230V/1Ph/50Hz
Motor type AC
Poles 4
Acoustic
Sound pressure 57.0 dB(A)
Sound power 88.9 dB(A)
Energy class E
Connections
Inlet 3"
Outlet 3"
Defrost
BC/BD-t-2X550AA5-B09 C None

Performance

Outlet 35 °C

Fluid inlet 35–60 °C (outlet = inlet − 5 K, at least 5 K above the air inlet); air inlet 25…50 °C.

WATER 40 → 35 °C, air inlet 25 °C

Heat rejection · Single phase
159.864 kW Fluid flow 27.74 m³/h Pressure drop 64.2 kPa

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)

WATER; rows: fluid inlet [°C], outlet = inlet − 5 K; columns: air inlet temperature. The highlighted cell is the nominal point. "—": not rated by the manufacturer.

Single phase

Heat rejection [kW]: Air inlet × fluid inlet (range 5 K)
Fluid inlet [°C] \ air [°C] 253035404550
35 89.92 not rated not rated not rated not rated not rated
40 159.86 90.52 not rated not rated not rated not rated
45 228.55 160.12 91.04 not rated not rated not rated
50 296.84 228.51 160.36 91.51 not rated not rated
55 364.95 296.52 228.49 160.61 91.96 not rated
60 432.96 364.36 296.27 228.55 160.91 92.41

Nominal rating

Nominal conditions: water 40 → 35 °C, air inlet 25 °C, relative humidity 50 %

Fan connection Heat rejection [kW] Fluid flow [m³/h] Pressure drop [kPa]
Single phase 159.864 27.74 64.2

Dimensions

Dimension drawing of BC/BD-t-2X550AA5-B09 C
Dimension drawing
Dimensions as drawn
A 4350 mm
B 1220 mm
C 1710 mm
F 1050 mm
G 450 mm
E 4100 mm
H 800 mm
I 1660 mm
K 4600 mm
D IN 3"
D OUT 3"
Overall [mm]
Length 4350 mm
Width 1800 mm
Height 1220 mm

Downloads

Ask about product

Our engineers answer with a selection for your conditions.

Thank you. We received your enquiry and will get back to you shortly.

The data are illustrative and may change without notice. Capacities are interpolated from the manufacturer's rating grid; points the manufacturer did not rate are shown as "not rated" and never estimated.

Compare 0 / 4 Open comparison You can compare up to 4 units; remove one before adding another.